A blog of all sections with no images
Frequency of Tests Print E-mail

Recommended Initial Frequencies of Inspection of Electrical Installations.

Type of Installation Routine check
sub clause 3.5
Maximum period between Inspections
and testing as necessary
Reference
see notes
below.

General Installation

Domestic
Commercial
Educational establishments
Hospitals
Industrial
Residential accommodation
Offices
Shops
Laboratories
See Sellers pack law
1 year
4 months
1 year
1 year
change of occupancy / 1 year
1 year
1 year
1 year
change of occupancy/10 years
change of occupancy/5 years
5 years
5 years
3 years
5 years
5 years
5 years
5 years
0.0
1.2
1.2
1.2
1.2
1.0
1.2
1.2
1.2

Buildings open to the public.

Cinemas 1 year
3 year
2,6,7
Church installations 1 year
5 years 2
Leisure complexes(no pools)
1 year
3 years 1,2,6
Public entertainment
1 year
3 years 1,2,6
Restaurants / Hotels
1 year
5 years 1,2,6
Theatres
1 year
3 years 2,6,7
Public houses / Bars
1 year
5 years 1,2,6
Village hall / centres 1 year 5 years 1,2

Special Installations

Agricultural / Horticultural 1 year 3 years 1,2
Caravans 1 year 3 years 0.0
Caravan Parks 6 Months 1 year 1,2,6
Highway power supplies as convenient 6 years 0.0
Marinas 4 Months 1 year 1,2
Fish farms 4 Months 1 year 1,2
Swimming pools 4 Months 1 year 1,2,6
Emergency lighting Daily / Monthly 3 years 2,3,4
Fire Alarms Daily/weekly/monthly 1 year 2,4,5
Laundrettes 1 year 1 years 1,2,6
Petrol stations 1 year 1 year 1,2,6
Construction sites 3 Months 3 Months 1,2

Reference Key:

1. Particular attention must be taken to comply with SI 1988 No1057. The electricity supply regulations 1988(as amended)
2. SI 1989 No 635. The electricity at work regulations 1989 (Regulation 4 & memorandum).
3. See BS 5266: Part1: 1988 Code of practice for the emergency lighting of premises other than cinemas and certain other specified premises used for entertainment.
4. Other intervals are recommended for testing operations of batteries and generators.
5. Se BS5839:Part1: 1988 Code of practice for system design installation and servicing (Fire detection and alarm systems for buildings).
6. Local authority conditions of license.
7. SI 1995 No 1129 (Clause 27) The cinematograph (Safety) Regulations.
 
 
Portable Appliance Testing Print E-mail

Portable Appliance Testing (P.A.T.)

A portable appliance is classed as any piece of equipment which can be connected to the common supply by means of a plug and socket arrangement. It must be maintained to be safe at all times. In effect any electrical equipment that has a mains plug on it.

While performing the tests we normally repair or relace damaged plugs and fuses. Our test equipement is always in calibration and is suitable for IT work.

Once the testing is complete you will have :

  • An asset list of all P.A.T. equipement
  • All the test data for any local authority requirement
  • A list of all Failures
  • This data is available (members area) securely, both viewable and printable for our customers who have an account on this website.
  • You will automatically receive a reminder when retesting is due. Timescale changes with individual clients.
 
Electrical Installation Testing. Print E-mail

Electrical Installation Testing

All aspects of the electrical installation are inspected and tested for strength, integrity and compliance with the IEE Regulations.

Any faults or defects found will be recorded, and a suggested method for correcting the fault will be given to you. Upon completion of the tests a complete schedule of the tests will include the following.

  • Periodic inspection certificate
  • Detailed circuit assessment sheets
  • Faults discovered while surveying
  • Survey report specific faults, locations & suggested solutions
  • Laminated circuit schedules, as required
  • Computer generated drawings
  • Dangerous conditions report

Electrical Testing for Safety

 
The electrical tests part 2 Print E-mail

8.6.1 - Testing earth electrodes

The earth electrode, where used, is the means of making contact with the general mass of earth. Thus it must be tested to ensure that good contact is made. A major consideration here is to ensure that the electrode resistance is not so high that the voltage from earthed metalwork to earth exceeds 50 V. Where an RCD is used, this means that the result of multiplying the RCD operating current (in amperes) by the electrode resistance (in ohms) does not exceed 50 (volts). for normal dry locations, or 25 (volts) for construction sites and agricultural premises.

If a 30 mA RCD is used, this allows a maximum electrode resistance of 1,666 Ohms, although it is recommended that earth electrode resistance should never be greater than 200 Ohms.A maximum value of 100 ohm is proposed in a draft amendment of BS 7430, Code of Practice for Earthing.

There are several methods for measurement of the earth electrode resistance. In all cases, the electrode must be disconnected from the earthing system of the installation before the tests commence.

Fig 8.13 - Measurement of earth electrode resistance with a dedicated tester

1. - Using a dedicated earth resistance tester

The instrument is connected as shown in {Fig 8.13} with terminals C1 and P1 being connected to the electrode under test (X). To ensure that the resistance of the test leads does not affect the result, separate leads should be used for these connections. If the test lead resistance is negligible, terminals Ci and P1 may be bridged at the instrument and connected to the earth electrode with a single lead.

Terminals C2 and P2 are connected to temporary spikes which are driven into the ground, making a straight line with the electrode under test. It is important that the test spikes are far enough from each other and from the electrode under test. If their resistance areas overlap, the readings will differ for the reason indicated in {Fig 8.14}. Usually the distance from X to Y will be about 25 m, but this depends on the resistivity of the ground. To ensure that resistance areas do not overlap, second and third tests are made with the electrode Z 10% of the X to Y distance nearer to, and then 10% further from, X. If the three readings are substantially in agreement, this is the resistance of the electrode under test. If not, test electrodes Y and Z must be moved further from X and the tests repeated.

The tester provides an alternating output to prevent electrolytic effects. If the resistance to earth of the temporary spikes Y and Z is too high, a reduction is likely if they are driven deeper or if they are watered.

 

Fig 8.14 - Effect of overlapping resistance areas
a) resistance areas not overlapping
b) resistance areas overlapping

 

2. - Using a transformer, ammeter and voltmeter

The system is connected as shown in {Fig 8.15}. Current, which can be adjusted by variation of the resistor R, is passed through the electrode under test (X) to the general mass of earth and hence to the test electrode Y. The voltmeter connected from X to Z measures the volt drop from X to the general mass of earth. The electrode resistance is calculated from:

voltmeter reading (V)
ammeter reading (A)

As in the case of the dedicated tester, the test electrode Z must again be moved and extra readings taken to ensure that resistance areas do not overlap. It is important that the voltmeter used has high resistance (at least 200 Ohms /V) or its low resistance in parallel with that of the electrode under test will give a false result.

 

Fig 8.15 - Measurement of earth electrode resistance
with a transformer, ammeter and voltmeter

 

3. - Using an earth fault loop impedance tester

The tester is connected between the phase at the origin of the installation and the earth electrode under test as shown in {Fig 8.16}. The test is then carried out, the result being taken as the electrode resistance although the resistance of the protective system from the origin of the installation to the furthest paint of the installation must be added to it before its use to verify that the 50 V level is not exceeded. If an RCD with a low operating current is used, the protective system resistance is likely to be negligible by comparison with the permissible electrode resistance.

Fig 8.16 - Measurement of earth electrode resistance using an earth-fault loop tester

It is most important to ensure that earthing leads and equipotential bonds are reconnected to the earth electrode when testing is complete.

8.6.2 - Measuring earth-fault loop impedance and
prospective short-circuit current

The nature of the earth-fault loop and its significance have been considered in detail in {5.3}. Since the loop includes the resistance of phase and protective conductors within the installation, the highest values will occur at points furthest from the incoming supply position where these conductors are longest. A measurement within the installation will give the complete earth-fault loop impedance far the point at which it is taken (Zs), or the earth-fault loop impedance external to the installation (Ze) may be measured at the supply position. Internal loop measurements should be taken at points furthest from the intake to give the highest possible results.

In simple terms, the impedance of the phase-to-earth loop is measured by connecting a resistor (typically 10 Ohms) from the phase to the protective conductor as shown in {Fig 8.17}. A fault current, usually something over 20 A, circulates in the fault loop, and the impedance of the loop is calculated within the instrument by dividing supply voltage by the value of this current. The resistance of the added resistor must be subtracted from this calculated value before the result is displayed. An alternative method is to measure the supply voltage both before and whilst the loop current is flowing. The difference is the volt drop in the loop due to the current, and loop impedance is calculated from voltage difference divided by current.

Fig 8.17 - Simple principle of earth-fault loop testing

 

Since the loop current is very high, its duration must be short and must be limited to two cycles (or four half-cycles) or 40 ms for a 50 Hz supply. The current is usually switched by a thyristor or a triac, the firing time being controlled by an electronic timing circuit It is very important to have already checked the continuity of the protective system before carrying out this test. A break in the protective system, or a high resistance within it, could otherwise result in the whole of the protective system being directly connected to the phase conductor for the duration of the test. Commercial testers are usually fitted with indicator lamps to confirm correct connection or to warn of reversed polarity. {Fig 8.18} shows a typical earth-fault loop tester connected to a socket outlet so that its loop impedance can be measured. If the circuit to be measured includes socket outlets, the tester is connected as indicated in {Fig 8.18}. Special leads for connection to phase and to earth are provided by suppliers for all other circuits.

Fig 8.18 - Earth-fault loop tester connected for use

Before testing, the main equipotential bonding conductors are disconnected (BUT NOT THE CONNECTION WITH EARTH) to prevent parallel earth return paths and to ensure that there is no reliance on the service pies for gas and water for effective earthing, (REMEMBER TO RECONNECT THE MAIN EQUIPOTENTIAL BONDING AFTER THE TEST).

Tests must be carried out at the origin of the installation, at each distribution board, at all fixed equipment, at all socket outlets, at 10% of all lighting outlets (choosing points farthest from the supply) and at the furthest point of every radial circuit. The test should be repeated at least once to allow for the effect of transient variations in the supply voltage.

A modified version of the earth-fault loop tester, which effectively measures the phase to neutral impedance and calculates then displays the value of the current which would flow if the supply voltage were applied to this impedance are readily available. The principle of such a PSC tester is described in {3.7.2}.

Since the test result is dependent on the supply voltage, small variations will affect the reading. Thus, the test should be repeated several times to ensure consistent results. The test resistor will be connected across the mains for the duration of each test. and will become very hot if frequent tests are made. Some testers will then 'lock out' to prevent further testing until the resistor temperature falls to a safe value.

The earth fault loop impedance measured as described will be for installation cables at ambient temperature, unless the circuit concerned has been in use immediately before the test, when it will be the impedance at normal operating temperature. Under normal operating conditions, cable temperature will rise, and so will the resistive component of the impedance. This effect is difficult to calculate, and a practical alternative is to ensure that the measured values of earth fault loop impedance do not exceed three quarters of the maximum values shown in {Tables 5.1, 5.2 or 5.4} as appropriate. 

A circuit protected by an RCD will need special attention, because the earth-fault loop test will draw current from the phase which returns through the protective system. This will cause an RCD) to trip. Therefore, any RCDs must be bypassed by short circuiting connections before earth-fault loop tests are carried out. It is, of course, of the greatest importance to ensure that such connections are removed after testing. One manufacturer supplies a patented loop tester which does not require RCDs to be short circuited and which will not cause them to trip

when the earth-fault loop test is made. Some instruments limit the test current to 15 mA so as not to trip RCDs with ratings of 30 mA and above. Whilst such tests may often be useful, they do not test the integrity of the system under fault current conditions.

When loop testing at lighting units controlled by passive infrared detectors (PIRs), there may he damage to the associated electronic switches unless they are short-circuited before testing.

An alternative to the use of a dedicated earth-fault loop impedance tester is to measure the combined resistance of the phase and protective conductors from the incoming position to the point for which earth-fault loop impedance is required (this is R1 + R2 - ) and to add to it the external earth-fault loop impedance (Ze) which can be obtained from the electricity supplier. All earth-fault loop impedance test results should be carefully compared with the data in [Tables 41B and 41D], adjusted to allow for ambient temperature, or with figures provided by the designer. To ensure that ambient temperature is taken into account, the results should never exceed three quarters of the values given in [Tables 41B and 41D].

8.6.3 - Testing residual current devices (RCDs)

Residual current devices should comply with BS 4293 and are described in (5.9), from which it will be seen that they are provided with a built-in self test system which is intended to be operated regularly by the user. BS 7671 requires that correct operation of this test facility should be checked, and that other tests are also carried out. The time taken for the device to operate must be measured, so the old type of 'go, no-go' tester is no longer adequate. {8.7.1} gives test instrument requirements.

RCD tests are carried out with a special tester which is connected between phase and protective conductors on the load side of the RCD after disconnecting the load {Fig 8.19}. A precisely measured current for a carefully timed period is drawn from the phase and returns via the earth, thus tripping the device. The tester measures and displays the exact time taken for the circuit to be opened. This time is very short, in most cases being between 10 and 20 ms, although it can be much longer, especially for S-types which have delayed operation

Fig 8.19 - Connections for an RCD tester

1. - General purpose non-delayed RCDs
This is a general purpose type of RCD which is intended to operate very quickly at its rated current. Three tests are required:

a) - 50% of the rated tripping current applied for 2 s should not trip the device,

b) - 100% of rated tripping current, which should not he applied for more than 2 s, must cause the device to trip within 200 ms (0.2 s), and

c) - where the device is intended to provide supplementary protection against direct contact, a test current of 150 mA, applied for no more than 50 ms, should cause the device to operate within 40 ms.

2. - Time-delayed RCDs
In {5.9.2} we discussed the need for discrimination between RCDs. This type is deliberately delayed in its operation to make sure that other devices which are connected downstream of it will operate more quickly. A 3:1 discrimination ratio is required between two RCDs which are connected in series, and this must be verified before testing. It means that the delayed RCD must have an operating current at least three times that of the non-delayed type. For example, to discriminate properly with a 30 mA device, a second connected on the supply side would need to have an operating current of at least 90 mA (in practice, a 100 mA RCD is likely to be used).

The test for the time-delayed RCD consists of applying 100% of the normal rated current, when the device should trip within the time range of:

For example, an RCD with a rated tripping time of 300 ms should trip within a time range of:

An RCD tester is an electronic device which draws current from the supply for its operation. This current is usually of the order of a few milliamperes which is taken from the phase and neutral of the supply under test, and will have no effect on the measurement of single-phase systems. However, if a three-wire three-phase system (there is no neutral with this supply) is being tested, the tester must be connected to a neutral conductor to provide the power it needs for operation. Thus, its operating current will flow through a line conductor and return through the neutral, giving a basic imbalance. A 'no-trip' test must also be carried out, during

 

Fig 8.20 - RCD tester connected for use

which the RCD must not operate when 50% of the rated tripping current is applied for 2 s. The extra current to power the tester, which adds to the test current, may then cause operation. It is necessary in this case to obtain from the RCD manufacturer the value of this current and to take it into account before failing a device on the 50% test.

The RCD tester is connected to the device to be tested by plugging it into a suitable socket outlet (see {Fig 8.20}) or by connecting to phase and neutral with special leads obtainable from the instrument supplier.

 

 

(150 + 200) ms     = 350 ms and
(300+200) ms       = 500 ms
50% of rated time delay plus 200 ms, and
100% of rated time delay plus 200 ms.
 
The electrical tests. Print E-mail

The electrical tests

 


8.4.1 - Protective conductor continuity

All protective and bonding conductors must be tested to ensure that they are electrically safe and correctly connected. Provided that the supply is not yet connected, it is permissible to disconnect the protective and equipotential conductors from the main earthing terminal to carry out testing. Where the mains supply is connected, as will be the case for periodic testing, the protective and equipotential conductors must not be disconnected because if a fault occurs these conductors may rise to a high potential above earth. In this case, an earth-fault loop tester can be used to verify the integrity of the protective system.

Where earth-fault loop impedance measurement of the installation is carried out, this will remove the need for protective conductor tests because that conductor forms part of the loop. However, the loop test cannot be carried out until the supply is connected, so testing of the protective system is necessary before supply connection, because connection of the supply to an installation with a faulty protective system could lead to danger.

There are three methods for measurement of the resistance of the protective conductor.

1. - Using the neutral conductor as a return lead
A temporary link is made at the distribution board between neutral and protective conductor systems. Don't forget to remove the link after testing. The low resistance tester is then connected to the earth and neutral of the point from which the measurement is taken (see {Fig 8.2}). This gives the combined resistance of the protective and neutral conductors back to the distribution board. Then

Rp = R x An
  An + Ap

 

where
Rp - is the resistance of the protective conductor
R - is the resistance reading taken
An - is the cross-sectional area of the neutral conductor
Ap - is the cross-sectional area of the protective conductor.

 

Note that the instrument reading taken in this case is the value of the resistance R1 + R2 calculated from This method is only valid if both conductors have the same length and both are copper; in most cases where steel conduit or trunking is not used as the protective conductor, the test will give correct results.

Fig 8.2 - Protective conductor continuity test using the
neutral conductor as the return lead

2. - Using a long return lead
This time a long lead is used which will stretch from the main earthing terminal to every point of the installation.

First, connect the two ends of this lead to the instrument to measure its resistance. Make a note of the value, and then connect one end of the lead to the main earthing terminal and the other end to one of the meter terminals.

Second, take the meter with its long lead still connected to the point from which continuity measurement is required, and connect the second meter terminal to the protective conductor at that point.

The reading then taken will be the combined resistance of the long lead and the protective conductor, so the protective conductor value can be found by subtracting the lead resistance from the reading.

Rp = R - RL
where
Rp - is the resistance of the protective conductor
R - is the resistance reading taken
RL - is the resistance of the long lead

Some modem electronic resistance meters have a facility for storing the lead resistance at the touch of a button, and for subtracting it at a further touch.

3. - Where ferrous material forms all or part of the protective conductor
There are some cases where the protective conductor is made up wholly or in part by conduit, trunking, steel wire armour, and the like. The resistance of such materials will always be likely to rise with age due to loose joints and the effects of corrosion. Three tests may be carried out, those listed being of increasing severity as far as the current-carrying capacity of the protective conductor is concerned. They are:

1 - A standard ohmmeter test as indicated in 1 or 2 above. This is a low current test which may not show up poor contact effects in the conductor. Following this test, the conductor should be inspected along its length to note if there are any obvious points where problems could occur.

2 - If it is felt by the inspector that there may be reasons to question the soundness of the protective conductor, a phase-earth loop impedance test should be carried out with the conductor in question forming part of the loop.

3 - If it is still felt that the protective conductor resistance is suspect, the high current test using 1.5 times the circuit design current (with a maximum of 25 A) may be used (see {Fig 8.3}. The protective circuit resistance together with that of the wander lead can be calculated from:

voltmeter reading (V)
ammeter reading (A)

Fig 8.3 - High-Current ac test of a protective conductor

Subtracting wander lead resistance from the calculated value will give the resistance of the protective system.

The resistance between any extraneous conductive part and the main earthing terminal should be 0.05 Ohms or less; all supplementary bonds are also required to have the same resistance.


8.4.2 - Ring final circuit continuity

The ring final circuit, feeding 13 A sockets, is extremely widely used, both in domestic and in commercial or industrial situations. It is very important that each of the three rings associated with each circuit (phase, neutral and protective conductors) should be continuous and not broken. If this happens, current will not be properly shared by the circuit conductors. {Fig 8.4} shows how this will happen. {Fig 8.4(a)} shows a ring circuit feeding ten socket outlets, each of which is assumed to supply a load taking a current of 3 A. In simple terms, current is then shared between the conductors, so that each could have a minimum current carrying capacity of 15 A. {Fig 8.4(b)} shows the same ring circuit with the same loads, but broken between the ninth and tenth sockets. It can be seen that now one cable will carry only 3 A whilst the other (perhaps with a current rating of 20 A) will carry 27 A. The effect will occur in any broken ring, whether simply one live conductor or both are broken.

 

Fig 8.4 - illustrating the danger of a break in a ring final circuit
a) unbroken ring with correct current sharing
b) broken ring with incorrect current sharing

It is similarly important that there should be no 'bridge' connection across the circuit. This would happen if, for example, two spurs from different points of the ring were connected together as shown in {Fig 8.5}, and again could result in incorrect load sharing between the ring conductors.

The tests of the ring final circuit will establish that neither a broken nor a bridged ring has occurred. The following suggested test is based on the Guidance Note on Inspection and Testing issued by the IEE.

 

Fig 8.5 - A 'bridged' ring final circuit

 

 

Test 1
This test confirms that complete rings exist and that there are no breaks. To complete the test, the two ends of the ring cable are disconnected at the distribution board. The phase conductor of one side of the ring and the neutral from the other (P1 and N2J are connected together, and a low resistance ohmmeter used to measure the resistance between the remaining phase and the neutral (P2 and Ni). {Figure 8.6} shows that this confirms the continuity of the live conductors. To check the continuity of the circuit protective conductor, connect the phase and CPC of different sides together (P1 and E2) and measure the resistance between phase and CPC of the other side (P2 and El). The result of this test will be a measurement of the resistance of live and protective conductors round the ring, and if divided by four gives (Ri + R2) which will conform with the values calculated from

Fig 8.6 - Test to confirm the continuity of a ring final circuit


Test 2
This test will confirm the absence of bridges in the ring circuit, see {Fig 8.7}. First, the phase conductor of one side of the ring is connected to the neutral of the other (P1 and N2) and the remaining phase and neutral are also connected together (P2 -and Ni). The resistance is then measured between phase and neutral contacts of each socket on the ring. If the results of these measurements are all substantially the same (within 0.05 Ohms), the absence of a bridge is confirmed. If the readings are different, this will indicate the presence of a bridge or may be due to incorrect connection of the ends of the ring. If they are connected P1 to NI and P2 to N2 then readings will increase or reduce as successive measurements round the ring are taken, as is the case where a bridge exists. Whilst this misconnection is easily avoided when using sheathed cables, a mistake can be made very easily if the system consists of single-core cables in conduit. It may be of interest to note that the resistance reading between phase and neutral outlets at each socket should be one quarter of the phase/neutral reading of Test 1.

Measurements are also taken at each socket on the ring between the phase and the protective conductor with the temporary connection made at the origin of the ring between P1 to E2 and between P2 to El. Substantially similar results will indicate the absence of bridges.

 

Fig 8.7 - Test to confirm the absence of bridges in a ring final circuit

 

8.5.1 - Testing insulation resistance

A low resistance between phase and neutral conductors, or from live conductors to earth, will result in a leakage current. This current could cause deterioration of the insulation, as well as involving a waste of energy which would increase the running costs of the installation. Thus, the resistance between poles or to earth must never be less than half of one meg ohm (0.5 M Ohms) for the usual supply voltages. In addition to the leakage current due to insulation resistance, there is a further current leakage in the reactance of the insulation, because it acts as the dielectric of a capacitor. This current dissipates no energy and is not harmful, but we wish to measure the resistance of the insulation, so a direct voltage is used to prevent reactance from being included in the measurement. Insulation will sometimes have high resistance when low potential differences apply across it, but will break down and offer low resistance when a higher voltage is applied. For this reason, the high levels of test voltage shown in {Table 8.8} are necessary.

Before commencing the test it is important that:

1. - electronic equipment which could be damaged by the application of the high test voltage should be disconnected. Included in this category are electronic fluorescent starter switches, touch switches, dimmer switches, power controllers, delay timers, switches associated with passive infrared detectors (PIRs), RCDs with electronic operation etc. An alternative to disconnection is to ensure that phase and neutral are connected together before an insulation test is made between them and earth.

2. - capacitors and indicator or pilot lamps must be disconnected or an inaccurate test reading will result.

Table 8.8 - Required test voltages and minimum resistance
Nominal circuit voltage

Test voltage
(V)
Minimum insulation resistance
(M Ohms)
Extra-low voltage circuits supplied from a safety transformer
250
0.25
Up to 500 V except for above
500
0.5
Above 500 V up to 1000 V
1000
1.0
The insulation resistance tester must be capable of maintaining the required voltage when providing a steady state of current of 1mA.

Where any equipment is disconnected for testing purposes, it must be subjected to its own insulation test, using a voltage which is not likely to result in damage. The result must conform with that specified in the British Standard concerned, or be at least 0.5 M Ohms if there is no Standard.

The test to earth {Fig 8.10} must be carried out on the complete installation with the main switch off, with phase and neutral connected together, with lamps and other equipment disconnected, but with fuses in, circuit breakers closed and all circuit switches closed. Where two-way switching is wired, only one of the two strapper wires will be tested. To test the other, both two-way switches should be

Fig 8.11 - Insulation tests between poles

operated and the system retested. If desired, the installation can be tested as a whole, when a value of at least 0.5 M Ohms should be achieved, see {Fig 8.10}. In the case of a very large installation where there are many earth paths in parallel, the reading would be expected to be lower. If this happens, the installation should be subdivided and retested, when each part must meet the minimum requirement.

The tests to earth {Fig 8.10} and between poles {Fig 8.11} must be carried Out as indicated, with a minimum acceptable value for each test of 0.5 M Ohms. However, where a reading of less than 2 M Ohms is recorded for an individual circuit, (the minimum value required by the Health and Safety Executive), there is the possibility of defective insulation, and remedial work may be necessary. A test result of 2 M Ohms may sometimes be unsatisfactory. If such a reading is the result of a re-test, it is necessary to consult the data from previous tests to identify deterioration. A visual inspection of cables to determine their condition is necessary during periodic tests; perished insulation may not always give low insulation readings

As indicated above, tests on SELV and PELV circuits are carried out at 250 V. However tests between these circuits and the live conductors of other circuits must be made at 500 V. Tests to earth for PELV circuits are at 250 V, whilst FELV circuits are tested as LV circuits at 500 V. Readings of less than 5 M will require further investigation.

 

8.5.2 - Tests of non-conducting floors and walls

Where protection against indirect contact is provided by a non-conducting location, the following requirements apply.

1. - there must be no protective conductors

2. - if socket outlets are used they must not have an earthing contact

3. - it should be impossible for any person to touch two exposed conductive parts at the same time

4. - floors and walls must be insulating.

To test this last item and so to make sure that the floors and walls are non-conducting, their insulation has to be tested.

The requirements are shown in {Fig 8.12}, the electrodes used for making contact

Fig 8.12 - Insulation test of floors and walls for non-conducting location

with floors and walls being a special type which are pressed onto the surface with a force of not less than 750 N (77 kg or 169 lb) for floors or 250 N (26 kg or 56 lb) for walls. The resulting insulation resistance of not less than three points on each surface, one of which must be between 1 m and 1.2 m from an extraneous conductive part (if there is one), measured at 500 V, must not be less than 0.5 MOhms. Attention is drawn to the natural reduction in the insulation resistance of a surface as humidity increases. Where insulation is applied to an extraneous conductive part to provide a non-conducting location, this insulation must be tested with an alternating p.d. of 2 kV. In normal use, the leakage current should not exceed I mA.

8.5.3 - Tests of barriers and enclosures

Throughout the Regulations reference is made to the use of barriers and enclosures to prevent contact with live parts (direct contact). If manufactured equipment's comply with the British Standards concerned, they will not need further testing, but where barriers and enclosures have been provided during erection of the installation, they must be tested.   The two most common tests are for:

1. - IP2X - no contact can be made with a probe 12 mm in diameter and 80 mm long
- in other words, a human finger

2. - IP4X - no contact can be made with a rod of diameter 1 mm.

8.5.4 - Tests for electrical separation of circuits

This section is concerned with tests necessary to ensure the safety of separated extra-low voltage (SELV), protective extra-low voltage (PELV) and functional extra-low voltage (FELV) circuits. In general, the requirement is a thorough inspection to make sure that the source of low voltage (most usually a safety isolating transformer) complies in all respects with the British Standard concerned, followed by an insulation test between the extra-low voltage and low voltage systems. The test is unusual in that a 500 V dc supply (from an insulation resistance tester) must be applied between the systems for one minute, after which the insulation resistance must not be less than 5 MOhms for SELV or PELV systems, or 0.5 MOhms for FELV systems. A further test at 3750 V dc for one minute is passed if no flashover occurs. This test in particular can be dangerous, and special care should be taken.

For SELV and FELV circuits, additional inspection must ensure that the low voltage requirements (not exceeding 50 V ac or 120 V dc) are met. If the voltage exceeds 25 V ac or 70 V dc (60 V ripple-free), barriers and enclosures must be tested to IP2X and a 500 V dc insulation test applied for one minute between the live conductors and metal foil wrapped round the insulation should produce a result of at least 0.5 MOhms

When insulation testing on electrically isolated circuits or on equipment which might be damaged by the test voltage, phase and neutral must be connected together and the test applied between them and earth.

 
Domestic electrical testing Print E-mail

Domestic Electrical Safety Testing to BS7671 (16th Editition)

There is little point in setting up Regulations to control the way in which electrical installations are designed and installed if it is not verified that they have been followed. For example, the protection of installation users against the danger of fatal electric shock due to indirect contact is usually the low impedance of the earth-fault loop; unless this impedance is correctly measured. this safety cannot be confirmed. in this case the test cannot be carried out during installation, because part of the loop is made up of the supply system which is not connected until work is complete.

In the event of an open circuit in a protective conductor, the whole of the earthed system could become live during the earth-fault loop test. The correct sequence of testing would prevent such a danger, but the tester must always be aware of the hazards applying to himself and to others due to his activities. Testing routines must take account of the dangers and be arranged to prevent them. Prominent notices should be displayed to indicate that no attempt should be made to use the installation whilst testing is in progress.

The precautions to be taken by the tester should include the following:

1. - make sure that all safety precautions are observed

2. - have a clear understanding of the installation, how it is designed and how it has been installed

3. - make sure that the instruments to be used for the tests are to the necessary standards (BS 4743 and BS 5458) and have been recently recalibrated to ensure their accuracy

4. - check that the test leads to be used are in good order, with no cracked or broken insulation or connectors, and are fused where necessary to comply with the Health and Safety Executive Guidance Note GS38

5. - be aware of the dangers associated with the use of high voltages for insulation testing. For example, cables or capacitors connected in a circuit which has been insulation tested may have become charged to a high potential and may hold it for a significant time.

 

8.2.1 - Notices and other identification

The installation tester, as well as the user, must have no difficulty in identifying circuits, fuses, circuit breakers, etc. Re must make sure that the installation is properly equipped with labels and notices, which should include:

I. - Labels for all fuses and circuit breakers to indicate their ratings and the circuits protected

2. - Indication of the purpose of main switches and isolators

3. - A diagram or chart at the mains position showing the number of points and the size and type of cables for each circuit, the method of providing protection from direct contact and details of any circuit in which there is equipment such as passive infra-red detectors or electronic fluorescent starters vulnerable to the high voltage used for insulation testing.

4. - Warning of the presence of voltages exceeding 250 V on an equipment or enclosure where such a voltage would not normally be expected.

5. - Warning that voltage exceeding 250 V is present between separate pieces of equipment which are within arm's reach

6. - A notice situated at the main intake position to draw attention to the need for periodic testing

7. - A warning of the danger of disconnecting earth wires at the point of connection of:

a). - the earthing conductor to the earth electrode

b). - the main earth terminal, where separate from main switchgear

c). - bonding conductors to extraneous conductive parts The notice should read Safety electrical connection - do not remove

8. - A notice to indicate the need for periodic testing of an RCD.

9. - A notice for caravans so as to draw attention to the connection and disconnection procedure as indicated in

10. - Warning of the need for operation of two isolation devices to make a piece of equipment safe to work on where this applies

11. - A schedule at each distribution board listing the items to be disconnected (such as semiconductors) so that they will not be damaged by testing.

12. - A drawing which shows clearly the exact position of all runs of buried cables.

8.3.1 - Why is correct sequence important?

Testing can be hazardous, both to the tester and to others who are within the area of the installation during the test. The danger is compounded if tests are not carried out in the correct sequence.

For example, it is of great importance that the continuity, and hence the effectiveness, of protective conductors is confirmed before the insulation resistance test is carried out. The high voltage used for insulation testing could appear on all extraneous metalwork associated with the installation in the event of an open-circuit protective conductor if insulation resistance is very low.

Again, an earth-fault loop impedance test cannot be conducted before an installation is connected to the supply, and the danger associated with such a connection before verifying polarity, protective system effectiveness and insulation resistance will be obvious.

Any test which fails to produce an acceptable result must be repeated after remedial action has been taken. Any other tests, whose results may have been influenced by the fault concerned must also be repeated.

8.3.2 - Correct testing sequence

Some tests will be carried out before the supply is connected, whilst others cannot be performed until the installation is energised. {Table 8.5} shows the correct sequence of testing to reduce the possibility of accidents to the minimum.

 

Table 8.5 - Correct sequence for safe testing

BEFORE CONNECTION OF THE SUPPLY
1
Continuity of protective conductors
2
Main and supplementary bonding continuity
3
Continuity of ring final circuit conductors
4
Insulation resistance
5
Site applied insulation
6
Protection by separation
7
Protection by barriers and enclosures
8
Insulation of non-conducting floors and walls
9
Polarity
10
Earth electrode resistance if an earth electrode resistance tester is used
WITH THE SUPPLY CONNECTED
11
Earth electrode resistance if an earth-fault loop tester or the ammeter and voltmeter method are used
12
Confirm correct polarity
13
Earth-fault loop impedance
14
Correct operation of residual current devices
15
Correct operation of switches and isolators
 
GadSolutions